32
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
Table 5. Base Card Setup
Setup
Rotary switches position Dip switch Enter button
Default
SW4 SW6 SW3 SW5
Close limit 0 0 ON PUSH n.d.
Open limit 1 0 ON PUSH n.d.
L/S close
2 1: by position ON PUSH 1
2 0: by torque ON PUSH
L/S open
3 1: by position ON PUSH 1
3 0: by torque ON PUSH
Closing speed
4 4 ON PUSH
4 6 ON PUSH 6
4 8 ON PUSH
Opening speed
5 4 ON PUSH
5 6 ON PUSH 6
5 8 ON PUSH
% Closing torque
6 2: 50% ON PUSH
6 5: 75% ON PUSH
6 9: 100% ON PUSH 9
% Opening torque
7 2: 50% ON PUSH
7 5: 75% ON PUSH
7 9: 100% ON PUSH 9
CW/CCW
8 0: CW; ON PUSH 0
8 1: CCW; ON PUSH
Size
9 0: 63 Nm / 250 Nm ON PUSH 0
9 1: 125 Nm / 500 Nm ON PUSH 0
9 3: 1000 Nm ON PUSH 0
9 4: 2000 Nm ON PUSH 0
Nm / lb-in
0 8: Nm ON PUSH 8
0 9: lb-in ON PUSH
Blinker / Local
Selector
4 0: Off ON PUSH 0
4 1: Blinker ON PUSH
4 2: Local Selector ON PUSH
Heater
8 9: Active ON PUSH 9
8 8: Not active ON PUSH
Inversion colors
LED of local
control
9 2 ON PUSH
LED
Open:Green
LED Close: Red
Remote Control 9
5 = 3-Wires
ON PUSH 5
6 = 2-Wires