34
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
6.2.5 Open Limit Conguration
Move switch SW 3 to position ON
Drive the actuator to open position using the handwheel.
Move switch SW 4 to position 1
Move switch SW 6 to position 0
Conrm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches ON for conrmation
Exit setup conguration by moving switch SW3 to position 1 or proceed with the
next parameter
6.2.6 Close Limit Conguration by Torque
Move switch SW4 to position 2
Move switch SW6 to position 0
Move switch SW3 to position ON
Conrm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to closing direction by local/remote control and wait until it
stops by torque
When the setting is complete, the red LED switches off
Exit setup conguration by moving switch SW3 to position 1 or proceed with the
next parameter
6.2.7 Open Limit Conguration by Torque
Move switch SW4 to position 3
Move switch SW6 to position 0
Move switch SW3 to position ON
Conrm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to opening direction by local/remote control and wait until it
stops by torque
When the setting is complete, the red LED switches off
Exit setup conguration by moving switch SW3 to position 1 or proceed with the
next parameter

Table of Contents