36
February 2020
Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
Actuator Configuration
Section 6: Actuator Configuration
6.2.9 Stroking Time Selection in Opening
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 5
• Move switch SW6 to positions 4, 6, 8 for the requested stroking time according to
the table below
• Push ENTER pushbutton SW5 to conrm
• When pushing SW5, the red LED switches on for conrmation
• The selected stroking time in opening is now set
• Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter
Table 6. Operating Times
Model
Nominal torque
(Nm / lb.ft)
Operating time (secs 90°) at selected step
8 6 4
063/E006 63/46 15 28 48
125/E013 125/92 15 28 48
250/E025 250/184 15 28 48
500/E051 500/369 15 28 48
1000/E091 1000/738 24 45 80
2000/E171 2000/1475 53 100 180
NOTE: Time is guaranteed with +/- 10% tolerance on 90° stroke
6.2.10 Setting of the Torque-Limiting Device in Closing
Closing torque limits are 50%, 75% and 100% of the nominal torque. The nominal torque
corresponding to 100% is set in-house and is stated on the nameplate.
• Enter setup conguration: move switch SW3 to position ON (conguration function)
• Move switch SW4 to position 6
• Move switch SW6 to positions 2, 5 or 9 for the requested torque value
(in percentage) in closing
• Push ENTER pushbutton SW5 to conrm
• When pushing SW5, the red LED switches on for conrmation
• The setting of the torque limiting device in closing stroke is now complete
• Exit setup conguration (move switch SW3 to position 1) or proceed to the
next parameter
NOTICE
Consult the valve manufacturer torque specications for correct limit torque conguration.
WARNING
Installation, conguration, commissioning, maintenance, and repairs must be performed
by approved and qualied personnel only.