Installation and Maintenance Instructions
MAN-02-04-99-0712-EN Rev. 1
February 2020
Actuator Configuration
Section 6: Actuator Configuration
6.3 Configuration of the SCE300 via PDA / PC and
A Manager’ Software
If one of the optional modules OM1, OM9, or OM11 is installed on the SCE300 and this card
features a Bluetooth interface, the actuator conguration can be performed by means of the
A Manager’ software installed on the PDA or PC.
Only the Blinker / Local Selector relay and heater cannot be congured via the ‘A Manager
software. The relevant Instruction and Operating Manual comes with the ‘A Manager’ software.
CAUTION
Emerson will not be held responsible - directly or indirectly - for any damage or injuries
caused by the misuse of external devices used for control or conguration of the actuator.
6.4 Hardware Configuration for Monitor Relay
The Monitor Relay indicates the following potential issues:
Loss of power
Stop by Torque out of limits
Direction failure
High Temperature
Position sensor failure
Local control panel with selector in local position
Jammed Valve
Hardware malfunction
Alarm on the local control panel (if present)
Stroke failure
Missing input 4-20 mA (if OM1 optional module present)
AManager local control (if Bluetooth is present)
Ensure that the power supply is off before attempting to congure the Monitor Relay.
The Monitor Relay contacts can be set as CLOSED or OPEN by changing the soldering of
JUMPER J31 on logic board. By default pins 2 and 3 are soldered together, and the Monitor
Relay contact operates as follows:
contact CLOSED in normal condition while the relay is energized, and
OPEN in case of malfunction (relay is de-energized).
By special request: if a contact must be OPEN under normal conditions and CLOSED when a
malfunction occurs, contact JUMPER J31 must be modied by soldering pins 1 and 2 together.
WARNING
Before performing service or maintenance operations (unless otherwise indicated), ensure
that power is turned off to the unit to avoid injury or damage to equipment.