C6.1.6/0613-0915/E 15
* G17 parameter >> Three defrost modes are available:
G17 = EL Defrost through electrical heater Compressor Off
G17 = in Hot gas defrost Compressor On
G17 = pulse Pulse / natural defrost Compressor Off
** G23 parameter >> Defrost interval mode:
G23 = nu (0) Defrost functionality not used
G23 = in (1) Defrost in intervals G18
G23 = rtC (2) → Enables defrost for RTC (real clock time), allows timing of defrost
cycles with G28 G41
*** G24 parameter >> Display during defrost:
G24 = DEF (0) Display shows "DEF" for defrost
G24 = SET (1) Display shows "G02" parameter value = Case temperature setpoint
G24 = IT (2) Display shows display case temperature value
G24 = RT (3) Display will stay in standard operation
**** G42 parameter >> Evaporator fans function:
G42 = cn (0) will switch On and Off with the compressor, Off during defrost
G42 = on (1) Fans On, even if the compressor is off, Off during defrost
o After defrost, there is a timed fan delay allowing for drip time, set by means of the
"G55" parameter.
G42 = cy (2) fans will switch On and Off with the compressor and On during defrost
G42 = oy (3) fans will run continuously also during defrost
Manual defrost
Please check settings for evaporator fans. The XCM-25D is able to control the evaporator fan.
NOTE: For additional features please contact your local Application Engineering
representative.
2.9 Electronic controller XCM25D Programming
2.9.1 Programming the local display
Figure 10: Local display
LED
Mode
Function
On
Compressor 1 enabled
Flashing
Anti-short cycle delay enabled
On
Condensing fans enabled
On
Bar display
Flashing
Programming mode
On
PSI display
Flashing
Programming mode
On
When browsing the service menu
Flashing
In fast access menu
On
When browsing the alarm menu
Flashing
A new alarm occurred