C6.1.6/0613-0915/E 40
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
-12°C to 12°C; -21°F to 21 °F
Not used (0-NU)
Ambient temp (NTC10K)(1-AMT)
Thermostat temp (NTC10K)(2-TMT)
Vapour inlet temp (NTC10K)(3-UIT)
Vapour outlet temp (NTC10K)(4-UOT)
Evaporator temp (NTC10K)(5-EPT)
Liquid temp (NTC10K)(6-LLT)
Suction line temp (7-SLT)
Coil temp (8-COT)
Delay before activating probe error
Measurement unit for pressure
bar(0-BAR) - PSI(1-PSI) - KPA(2-TPA)
Measurement unit for temperature
Remote display visualization
P1(0-P1) - P2(1-P2) - P3(2-P3) - P4(3-P4) - P5(4-P5) –
P6(5-P6) - P7(6-P7) - PEr(7-PER) - Aou(8-AOU)
Filter enabling for probe reading
Coefficient for probe reading filter (0 = max,100 = disable)