C6.1.6/0613-0915/E 41
Code
Description
Range
Factory Setting
ZXDE
ZXME
ZXLE
C01
Compressor cut in pressure set point
CoU to US;
4
N.V.
L1
L1
C02
Compressor cut out pressure set point
LS to Cin;
2
L2
L1
L1
C03
Minimum set point for suction pressure/temperature
P1i to US; -50.0°C to US
0.6
L2
L2
L2
C04
Maximum set point for suction pressure/temperature
LS to P1E; LS to 60.0°C;
6.3
L2
L2
L2
C05
Compressor regulation probe selection
NU (0-NU)
Suction pressure probe (1-SUP)
Case temperature (2-CST)
Suction pressure switch (3-dIS)
Suction pressure probe
L2
L2
L2
C06
EXV closing time before compressor off
0 to 999 sec
0
L2
L2
L2
C07
Refrigerant selection for regulation
R404A(0-404) - R507(1-507) - R134A(2-134) - R22(3-
R22) - R407C(4-07C) - R407A(5-07A) - R407F(6-07F) -
N40(7N40) - DR33(8-R33) - R410A(9-410)
R404A
L1
L1
L1
C08
Set point offset
NU (0-NU)
Small offset (1-SOF)
Medium offset (2-MOF)
Large offset (3-LOF)
LAO (4-FOF)
NV
L2
L2
L2
C09
Ambient temperature operation set point
-40°C to 110°C;'-40 to 230°F
-20
L2
L2
L2
C10
Pressure/Temperature operation for ambient differential
0.0Bar to 9.9Bar; 0.0PSI to 99.9PSI
0.0°C to 25.5 °C
1
L2
L2
L2
C11
Ambient temperature recover differential
0.1°C to 25.5 °C
5
L2
L2
L2
C12
Ambient temperature threshold for low ambient operation
-40°C to 110°C
-10
L2
L2
L2
C13
Temperature/Pressure to end low ambient timer and resume normal
operation
-40°C to 110°C
'-1.5 to 99.9 bar; -21 to 999 PSI
10
L2
L2
L2
C14
Compressor minimum on time in low ambient operation
0 to 255 sec
10
L2
L2
L2
C15
Pressure to end low ambient timer and shut off the compressor
-1.5 to 99.9 bar; -21.0 to 999 PSI
0.5
L2
L2
L2
C16
Digital compressor set point
LS to US
3.3
L1
N.V.
N.V.
C17
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to 25.5°C
2
L1
N.V.
N.V.
C18
Band offset for compressor regulation
0 to 9.9 bar; 0 to 99.9 PSI; 0.0°C to 25.5°C
0
L2
N.V.
N.V.
C19
Integral time
0 to 999 sec
250
L2
L2
N.V.
C20
Startup time: interval time with digital valve energized before start
regulation
0.0 to 10.0 sec
10
L2
N.V.
N.V.
C21
Cycle time for digital compressor
10 to 40 sec
10
L1
N.V.
N.V.
C22
Safety value for PI regulator (in case of probe error)
0 to 100%
50
L2
N.V.
N.V.