C6.1.6/0613-0915/E 41
Compressor cut in pressure set point
Compressor cut out pressure set point
Minimum set point for suction pressure/temperature
Maximum set point for suction pressure/temperature
Compressor regulation probe selection
NU (0-NU)
Suction pressure probe (1-SUP)
Case temperature (2-CST)
Suction pressure switch (3-dIS)
EXV closing time before compressor off
Refrigerant selection for regulation
R404A(0-404) - R507(1-507) - R134A(2-134) - R22(3-
R22) - R407C(4-07C) - R407A(5-07A) - R407F(6-07F) -
N40(7N40) - DR33(8-R33) - R410A(9-410)
NU (0-NU)
Small offset (1-SOF)
Medium offset (2-MOF)
Large offset (3-LOF)
LAO (4-FOF)
Ambient temperature operation set point
-40°C to 110°C;'-40 to 230°F
Pressure/Temperature operation for ambient differential
0.0Bar to 9.9Bar; 0.0PSI to 99.9PSI
0.0°C to 25.5 °C
Ambient temperature recover differential
Ambient temperature threshold for low ambient operation
Temperature/Pressure to end low ambient timer and resume normal
operation
-40°C to 110°C
'-1.5 to 99.9 bar; -21 to 999 PSI
Compressor minimum on time in low ambient operation
Pressure to end low ambient timer and shut off the compressor
-1.5 to 99.9 bar; -21.0 to 999 PSI
Digital compressor set point
Proportional band for compressor regulation
0.1 to 9.9 bar; 0.1 to 99.9 PSI; 0.1°C to 25.5°C
Band offset for compressor regulation
0 to 9.9 bar; 0 to 99.9 PSI; 0.0°C to 25.5°C
Startup time: interval time with digital valve energized before start
regulation
Cycle time for digital compressor
Safety value for PI regulator (in case of probe error)