Appendix 5: Alarm menu
Code
Description
Cause
Action
Reset
E01
AI1 error (Probe 1/Suction pressure
transducer failure alarm)
Probe failure or out
of range
Only in digital unit - compressor is
activated according to C23, and
compressor on & off time is according
to D02 & D03
Automatically as soon as the probe restarts
working
E02
AI2 error (Probe 2/mid-coil
temperature sensor failure alarm)
Probe failure or out
of range
The fan speed control is disabled
Automatically as soon as the probe restarts
working
E03
AI3 error (Probe 3/discharge line
temperature sensor failure alarm)
Probe failure or out
of range
Discharge temperature control is
disabled
Automatically as soon as the probe restarts
working
E04
AI4 error (Probe 4/PHE vapor inlet
temperature sensor failure alarm)
Probe failure or out
of range
PHE super heat control is disabled
(ZXL/ZXB unit)
Automatically as soon as the probe restarts
working
E05
AI5 error (Probe 5/PHE vapor outlet
temperature sensor failure alarm)
Probe failure or out
of range
PHE super heat control is disable
d(ZXL/ZXB unit)
Automatically as soon as the probe restarts
working
E06
AI6 error (Probe 6/ambient
temperature sensor failure alarm)
Probe failure or out
of range
The functions related to probe 6
(ambient sensor) is disabled
Automatically as soon as the probe restarts
working
E07
AI7 error (not used in Asia)
Probe failure or out of range(not used in Asia)
E08
Battery error
E09
Current sensor 1 error
Probe out of range
The functions related to current sensor
is disabled
Automatically as soon as the probe restarts
working
E10
Current sensor 2 error
Probe out of range
The functions related to current sensor
is disabled
Automatically as soon as the probe restarts
working
E11
Voltage sensor 1 error
Probe out of range
The functions related to voltage sensor
is disabled
Automatically as soon as the probe restarts
working
E12
Voltage sensor 2 error
Probe out of range
The functions related to voltage sensor
is disabled
Automatically: as soon as the probe restarts
working
E13
Voltage sensor 3 error
Probe out of range
The functions related to voltage sensor
is disabled
Automatically as soon as the probe restarts
working
E14-E19
Reserved