C6.1.6/0613-0915/E 58
High condenser pressure alarm
High condenser temperature alarm
Condenser
temperature larger
than E58 for E59
minutes
The compressor is activated according
to E60
Automatically: as soon as condenser
temperature lower than E61
EXV full open for F40
minutes
Automatically: as soon as EXV is not at
maximum steps
Refrigerant shortage error in EVI
EXV full open and
PHE super heat is
larger than
(F28/F29…/F37 +
F39)
Automatically: as soon as PHE super heat is
lower than (F28/F29…/F37 + F39)
(F28/F29…/F37 depends on refrigerant type)
High side floodback alarm
The differential
temperature between
discharge and mid-
coil is lower than H21
for accumulated H22
minutes in H23
minutes
Automatically: as soon as differential
temperature between discharge and mid-coil is
larger than H21 for H24 minutes
Max pressure alarm of superheating
Min pressure alarm of superheating
High room temperature alarm
Low room temperature alarm
Table 30: Alarm code overview