C6.1.6/0613-0915/E 61
Defrost with Real Time Clock
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
NU = Not used
Ept = Evaporator temperature
G12
Defrost probe selection
NU = Not used
Ept = Evaporator temperature
G23
Defrost interval mode
NU = Not used
Rtc - Real time clock
S05
Relay Output 2
NU = Not used
DEF = Defrost
G18
interval between defrost cycles
4
Adjust to application requirements
G19
Maximum length for defrost
20
Adjust to application requirements
G21
Defrost termination temperature
10
Adjust to application requirements
G26
Drip time
1
Adjust to application requirements
G28-41
See tables "Parameter list level 2"
[-]
Adjust to application requirements
Defrost with evaporator fan
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
NU = Not used
Ept = Evaporator temperature
G12
Defrost probe selection
NU = Not used
Ept = Evaporator temperature
G23
Defrost interval mode
NU = Not used
IN - by time (G18)
G42
Fans operating mode
Cn
OY
S05
Relay Output 2
NU = Not used
EPF = Evaporator fan
G18
interval between defrost cycles
4
Adjust to application requirements
G19
Maximum length for defrost
20
Adjust to application requirements
G21
Defrost termination temperature
10
Adjust to application requirements
G26
Drip time
1
Adjust to application requirements
G55
Fan delay after defrost
1
Adjust to application requirements