C6.1.6/0613-0915/E 62
Evaporator fans
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
NU = Not used
tnt = Thermostat temperature
G47
Room probe selection for evaporator fan management
NU = Not used
tnt = Thermostat temperature
S05
Relay Output 2
NU = Not used
EPF = Evaporator fan
G42
Fans operating mode
Cn
Adjust to application requirements
G43
Fans stop temperature
0
Adjust to application requirements
G44
Temperature differential avoiding short cycles of fans
2
Adjust to application requirements
G45
Fan On time
1
Adjust to application requirements
G46
Fan Off time
1
Adjust to application requirements
G55
Fan delay after defrost
1
Adjust to application requirements
System EXV
Parameter
Parameter description
Factory setting
Required setting
A19
Probe 7 configuration
NU = Not used
SLt = Suction line temp
L02
Set of superheating
5
7
S11
EXV configuration
UIN or LIN
SHT = System superheat
Door switch
Parameter
Parameter description
Factory setting
Required setting
G08
Compressor and fan status when open door
Fn
Fn - Stop fan
R07
Digital input 3 configuration
NU = Not used
DOR = Door
G53
Maximum door open time before alarm
3
Adjust to application requirements
R08
Digital input 3 polarity
Cl = Closed
Adjust to application requirements
Table 31: Additional features for customization