Recommended settings / Comments
Evaporator temp (NTC10K) = 5 = EPt
5 = Evaporator temperature sensor = EPt
0 = Electrical = EL; 1 = Hot gas defrost
(not available on ZX units) = in;
2 = Natural defrost (pulse defrost) = PLS
Interval between
defrost cycles
0 to 120 hours range; adjust to individual
requirements
Maximum duration
of defrost
0 to 255 minutes; adjust to individual
requirements
Duration of pulse
defrost
Defrost
termination
temperature
0 = nu = Not used; 1 = in = Interval;
2 = rtC = Real time clock
0 = dEF = Defrost;
1 = Set = Case temperature setpoint;
2 = it = Case temperature value;
3 = rt = Standard operation
Maximum display
delay after defrost
Avoids defrost after initial power up. If
"YES", the controller will decide on defrost
related parameters if a defrost sequence is
required after initial start-up
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used
00:00 – 23:50 or nu = Not used