Display, actions and settingsTable 6-1:
Parameter Display Action/Setting
Advanced ADVANCE Enter Advanced menu
Output OUTPUT Setup open collector outputs Out 1 and
Out 2
Output 1 OUT 1 Assign function of pulse output 1
Output 2 OUT 2 Assign function of pulse output 2
Pulse PuLSE Set Out 1 or Out 2 for pulse output mode
Rate rAtE Assign pulse output to rate
Total totAL Assign pulse output to total
Grand total Grtot Assign pulse output to grand total
Decimal point dec.Pt Set K-factor decimal point
Count count Set K-factor
Retransmit rEtr Assign pulse output to retransmit
Quadrature quAd Assign pulse output to quadrature
Test tESt Assign pulse output to test mode
Alarm ALrm Assign Out 1 or Out 2 for alarm output
mode
Rate rAtE Assign alarm output to rate
Set point SEt Set rate alarm set point
Reset point rESEt Set rate alarm reset point
Total totAL Assign alarm output to total
Grand total Grtot Assign alarm output to grand total
Set point SEt Set total or grand total alarm set point
On On Set output to on state
Off Off Set output to off state
Timer tmEr Set Out 1 or Out 2 for timed pulse output
mode
Start StArt Activate timed pulse output
Delay deLAY Set the time of one period (seconds)
On On Set the active low pulse width
Off Off Set Out 1 or Out 2 as off
Analog output A OUT Enter Analog Output menu
Rate output rAtE Set rate as output variable
Total output totAL Set total as output variable
Grand total output Grtot Set grand total as output variable
Display 1 dSP 1 Output display 1 value
Output 1 OUT 1 Output 1 value
Product advanced features
User manual 55