1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 126/192
Pump down pressure switch : CO36 = 1, 2, 3, 4 and compressors start-up and
digital input not active for the time set in CO39
Pump down transducer: CO36 = 1, 2, 3, 4, compressors start-up and the set
CO37 is not reached in the interval time CO39.
From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 +
CO38 (differential)
Automatic - Manual and logged after AL21 events per hour if AL23=1 (reset
procedure in function menu).
If AL23 = 0 it is automatic and not logged.
On the display the symbol is blinking
Alarm relay + buzzer ON when it becomes manual
b1rC – b2rC recovery disabled from high condensing temperature/pressure in Chiller
Label on alarm
visualization menu
b1rC (recovery disabled message from circuit 1)
b2rC (recovery disabled message from circuit 2)
In normal running condition when the temperature/pressure probe value is
higher than the set rC06
When the temperature/pressure probe value is lower than the rC06 –
rC07(differential)
Unloading start after the time delay Par. rC08
On the display the symbol is blinking
b1tF- b2tf Condenser fan overload alarm
Label on alarm
visualization menu
b1tF (Condenser fan overload alarm of the circuit #1)
b2tF (Condenser fan overload alarm of the circuit #2)
When the digital input is active
When the digital input is not active
Manual (reset from the function menu)
On the display the symbol is blinking
b1UA, b2UA Expansion valve 1 or Expansion Valve 2 Alarm
Label on alarm
visualization menu
b1UA (expansion valve 1 alarm)
b2UA (expansion valve 2 alarm)
When the electronic expansion valve is on alarm
Automatic when the alarm is solved
C1dt - C2dt - C3dt - C4dt – C5dt - C6dt High compressor discharge temperature alarm
Label on alarm
visualization menu
C1dt (High discharge temperature of the compressor 1) -…C6dt (High
discharge temperature of the compressor 6)
The compressor discharge temperature is higher than AL39 setpoint.
ATTENTION
The display resolution is 0.1°C until the read-out is 99.9, over 100°C it is 1°C.