1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 127/192
If the probe value of the high discharge temperature is lower than “AL39 -
AL40 (differential)”
Automatic. Manual when there are AL41 per hour (Reset procedure in Menu
function).
On the display the symbol is blinking
Alarm Relay and buzzer on
C1HP - C2HP - C3HP - C4HP- C5HP – C6HP compressor high pressure alarms
Label on alarm
visualization menu
C1HP ( compressor 1 high pressure alarm) – … C6HP (compressor 6 high
pressure alarm)
The unit is running and the digital input of the compressor high pressure switch
is active
Reset procedure in Menu function
Reset procedure in Menu function
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
On the display the symbol is blinking
Alarm Relay + and buzzer on
If FA02=0 the fan is forced at maximum speed for 60 seconds then switched
off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate
according to normal fan regulation
C1Mn - C2Mn - C3Mn - C4Mn – C5Mn – C6Mn -Compressor maintenance
Label on alarm
visualization menu
C1Mn (Compressor 1 maintenance) –…C6Mn (Compressor 6 maintenance)
Compressor running hours > Hour counter setpoint
Hour reset in function menu
On the display the symbol is blinking
Only display warning messages
C1oP - C2oP - C3oP - C4oP - - C5oP – C6oP Pressure switch alarm / compressor oil
Label on alarm
visualization menu
C1oP (Compressor 1pressure switch … C6oP (Compressor 6 pressure switch)
The alarm is not signalled: during the AL01 delay after turning on the
compressor, during the AL12 delay that starts after the AL11 delay when the
unit is properly running
Automatic - Manual after AL013 events per hour (Reset procedure in Menu
function).
If AL76=1 the alarm is only a warning and the compressor remains on
On the display the symbol is blinking
Alarm Relay + and buzzer on