1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 149/192
EI 37
I/O expansion RL5 configuration
0
c80
EI 38
I/O expansion RL6 configuration
0
c80
EI 39
I/O expansion RL7 configuration
0
c80
EI 40
I/O expansion 0-10V / 4-20mA output selection
0
1
EI 41
I/O expansion proportional output OUT 1
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
o1..c50 ON / OFF with the same meaning of reconfiguration
0
o 1
9
c54
EI 42
I/O expansion proportional output OUT 2
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of re
0
o 1
11
c54
EI 43
I/O expansion proportional output OUT 3
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of re
0
o 1
11
c54
Parameter
Description
min
max
M. u.
Resolution
Sd 1
Maximum dynamic Offset in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 2
Maximum dynamic Offset in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 3
External air setpoint in chiller mode
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 4
External air setpoint in heat pump mode
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 5
External air differential in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 6
External air differential in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 7
Dynamic set point: summer offset analog 1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 8
Dynamic set point: winter offset analog 1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 9
Summer outside temperature analog 1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 10
Winter outside temperature analog 1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 11
Summer outside temp. differential analog 1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 12
Winter outside temp. differential analog 1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 13
Dynamic set point: summer offset analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 14
Dynamic set point: winter offset analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int