DL8000 Preset Instruction Manual
D-72 Communications Protocols Revised February-2016
Report Alarm
[0x3D]
Raises an alarm based on alarm code received in the command request
frame. Possible uses of this command are:
Raising an alarm based on conditions that are either not input to or
detectable by DL8000 (such as a fire detection system or a PLC being
used to monitor a rail car’s position).
Stopping a batch with a situation-specific message. In this case, the
automation system might configure a safety circuit alarm message via
communications and then raise the corresponding safety circuit alarm. The
automation system can reset the alarm using the Reset primary alarms
command [0x14].
Note: A TAS should not depend on DL8000 alarms to prevent or control
hazardous or life threatening conditions.
Primary Alarm active (if primary alarm is raised)
Flags Immediately
Cleared
None
Exceptions
Invalid bit no. (that is, the alarm code in the
command request frame is invalid)
Unable to set or reset alarm
Supporting
Alarm ID [63,0,173]
Batch may stop due to reported alarm.
Deviations
Comm B is not supported.
Supports additional exception code “Unable to
set or reset alarm”
Does not support the following DanLoad 6000
protocol alarms:
• Data logging memory full
• Memory Check Failure
• Primary Display Failure
• Secondary Display Failure
• MPMC 1 and MPMC 2 Failure
• Calibration Failure for all meters
• Intermediate Level Input