E300 Design Guide 129
Issue Number: 1
6.3 Full parameter descriptions
A00 (Parameter Zero A00)
A01 (User Security Status H02)
This parameter controls access via the drive keypad. The keypad can be used to adjust this parameter even when user security is set.
A02 (Drive Control Mode B01)
This parameter defines the drive operating mode. Pr mm00 must be set to ‘1253’ (European defaults) or ‘1254’ (USA defaults) before this parameter
can be changed. When the drive is reset to implement any change in this parameter, the default settings of all parameters will be set according to the
drive operating mode selected and saved in memory.
The parameter settings for the drive mode are as follows:
A03 (Parameter Cloning Modes N01) can be used to initiate data transfers to or from an NV Media Card as described below. Only a value of Auto (3)
or Boot (4) can be saved in this parameter.
1: Read
Setting A03 (N01) = Read (1) and initiating a drive reset will transfer the parameter data to the drive. When the action is complete this parameter is
automatically reset to zero.
2: Program
Setting A03 (N01) = Program (2) and initiating a drive reset will transfer the parameter data from the drive to a parameter file with file identification
number 1 (any existing file will be overwritten). When the action is complete this parameter is automatically reset to zero.
A00 {A00} Parameter Zero
RW Num ND NC PT
Ú
0 to 65,535
Ö
A01 {H02} User Security Status
RW Txt ND PT
OL
Ú
User menu A (0), All
Menus (1), Read-only
User menu A (2),
Read-only (3),
Status Only (4),
No Access (5)
Ö
RFC-A
RFC-S
Security level Description
0 (User menu A) All writable parameters are available to be edited but only parameters in User menu A are visible.
1 (All Menus) All writable parameters are visible and available to be edited.
2 (Read-only User menu A) All parameters are read-only. Access is limited to User menu A parameters only.
3 (Read-only) All parameters are read-only however all menus and parameters are visible.
4 (Status Only) The keypad remains in status mode and no parameters can be viewed or edited.
5 (No Access)
The keypad remains in status mode and no parameters can be viewed or edited.
Drive parameters cannot be accessed via a comms / fieldbus interface in the drive or any option module.
A02 {B01} Drive Control Mode
RW Txt ND NC PT US
OL
Ú
Open loop (1)
Ö
Open loop (1)
RFC-A RFC-A (2)
Ö
RFC-A (2)
RFC-S RFC-S (3)
Ö
RFC-S (3)
Setting Operating mode
1 Open loop
2RFC-A
3RFC-S
A03 {N01} Parameter Cloning
RW Txt NC US
OL
Ú
None (0), Read (1),
Program (2), Auto (3),
Boot (4)
Ö
None (0)RFC-A
RFC-S