FB1100/FB1200 Flow Computer Termination Board Field Replacement Guide
D301
820X012
10
14. You should be able to see through the housing from back to front and see the
opposite end of the captive fastening screws that you saw in Steps 11 and 12.
15. Take the new (replacement) termination board (399185-01-1 or 400216010-KIT),
and align it with the captive fastening screw holes and press it into the back of the
housing onto the captive fastening screws.
16. Tighten the screws that you loosened in Step 12. Torque screws to 6 in-lbs (0.7 N
m).
17. Take the battery pack enclosure/HMI module assembly you removed in Step 8.
Being careful to keep the battery wire and its connector free, carefully slide the
assembly into the front of the housing so that the HMI module mates with the
green and yellow connector from the CPU module. Tighten the screws to hold the
assembly in place. Torque screws to 6 in-lbs (0.7 N m). If battery-powered, re-
connect the battery.
18. You can now proceed to rewire all connections (I/O, communications, grounding)
to the flow computer. Please refer to the instruction manual for wiring installation
instructions.