Instruction Manual
D101322X012
1051 and 1052 Size 33 Actuators
June 2017
9
DESIRED
ACTUATOR
ACTION
DESIRED
SHAFT
ROTATION,
DEGREES
ACTUATOR
MOUNTING
POSITION
COUPLING
KEYWAY
TO USE
(3)
VALVE SHAFT KEYWAY TO USE FOR FISHTAIL™
DISC VALVE BODIES
(1)
(SEE FIGURE 2)
Clockwise to
Close Valve Action
(2)
Counterclockwise to
Close Valve Action
(2)
Flow Left
to Right
(2)
Flow Right
to Left
(2)
Flow Left
to Right
(2)
Flow Right
to Left
(2)
Push Down to Open
(PDTO)
60 or 90
1 B Nose Tail Tail Nose
2 A Tail Nose Nose Tail
3 B Tail Nose Nose Tail
4 A Nose Tail Tail Nose
Push Down to Close
(PDTC)
60
(3)
or 90
1 A Tail Nose Tail Nose
2 B Tail Nose Tail Nose
3 A Nose Tail Nose Tail
4 B Nose Tail Nose Tail
1. For conventional disc valve bodies, use either valve shaft keyway.
2. When viewed from actuator side of valve body.
3. For 60‐degree rotation with PDTC action, the coupling and actuator output shaft assembly will offset 30 degrees clockwise (for actuator housing construction style B), or counterclock
wise (for actuator housing construction Style A) in the lever when viewed from the splined end of the actuator shaft. 30 degrees is one spline tooth for 9.5, 12.7, and 15.9 mm (3/8, 1/2,
and 5/8 inch) valve shafts and two spline teeth for 19.1 mm (3/4 inch) valve shafts.
Figure 4. Valve Shaft Coupling for the J Mounting Adaptation
A3253*
19A1465‐B
NOTES:
FOR USE WITH J MOUNTING ADAPTATION.
COUPLING
FULL KEYWAY
LOCATED ON
NOSE AND TAIL
SIDE OF VALVE SHAFT
VALVE SHAFT
PARTIAL KEYWAY
FOR DETERMINING
DISC POSITION
USE APPROPRIATE
VALVE SHAFT
KEYWAY AS
INDICATED
IN TABLE 5
USE APPROPRIATE LETTERED
KEYWAY AS INDICATED IN
TABLE 5
KEYWAY A
KEYWAY B
ABOVE
KEYWAY A
EXPLODED VIEW OF VALVE SHAFT
AND COUPLING
REFERENCE COUPLING ORIENTATION
FOR TABLE 5
1
1
WARNING
To avoid personal injury and equipment damage from moving parts, keep fingers and tools clear while stroking the
actuator with the cover removed.
9. Stroke the actuator and adjust the down travel stop so that the valve ball or disc is in the desired position.
10. Make sure that the travel indicator pointer matches the ball or disc position. Remove and install in the proper
position if necessary.