Operation
17 Liebert
®
NXL
Battery Management
These DC source settings can be changed from the touchscreen. Press the box to the left of each
parameter to bring a popup window that will allow the parameter to be changed.
Battery Equalize
When Battery Equalize is activated (Manual Battery Equalize button under Batt Mgt), the module
will charge the batteries to the Equalize Voltage for the length of Equalized Time.
Equalize Voltage, Vpc - 2.30 to 2.45 (default: 2.3)
Equalize Time, hours - 0 to 200hours (default: 0)
Figure 19 Battery Equalize settings
Battery Test
Auto Test—Enable/Disable (default: disabled)
Test Cycle, weeks—1 to 26 (default: 13 weeks)
Time of day, hh:mm—Set Hour and Minute; sets the start time of the automatic battery test
Start Date, mm dd, yyyyy—Set Month, Day and Year
Test Duration, minutes—0.5 minute to 30% of full load Operating Time (default: 0.5 minute)
Minimum Battery Voltage, lead-acid only—1.75VPC to 1.95VPC (default: 1.75VPC); this is the
minimum voltage the battery test will stop.
Low Battery Warning Time
Low Battery Warning Time, minutes—2 to 60, the upper limit is dependent on configured
batteries (default: 5 minutes)
Battery Temperature
Battery Temp Warning—30°C to 50°C (default: 40°C)
Battery Temp Limit—35°C to 60°C (default: 50°C)
Disconnect—Enable/Disable (default: disabled)
NOTE
Battery Equalize must be enabled by service to be functional. If Battery Equalize is disabled,
the feature will not be available and the menu item will not be displayed.