A Wire the 1600 to the 3100 relays
Use this procedure to wire the Discrete Output on the 1600 Ethernet transmitter to the
3100 transmitter relays for single-stage batch control.
Prerequisites
Set up the Channel B configuration to DO before wiring
Use active high and internal power.
Use wire size 24 AWG (0,25 mm
2
) to 16 AWG (1,5 mm
2
).
Procedure
1. Wire the negative terminal on Channel B from the 1600 Ethernet transmitter to
A14.
2. Wire the positive terminal on Channel B from the 1600 Ethernet transmitter to
either C14, C16, or C18.
Figure A-1: Wiring for 1600 Ethernet Channel B DO to 3100 relays
F3
C A
IEC 127-2
J 3
DISC
OUT 3
T5A 250V
C A
F1
C A
IEC 127-2
J 1
J 4
DS1
T5A 250V
K3 K2 K1
A B C
DISC
OUT 2
IEC 127-2
F2 T5A 250V
J 2
DS2
DISC
OUT 1
DS3
C18
C16
C14
A14
Installation Manual Wire the 1600 to the 3100 relays
00825-0100-1600 March 2022
Installation Manual 47