9 I/O wiring for Model 2700
transmitters with configurable input/
outputs
Topics covered in this chapter:
Channel configuration
mA/HART wiring
Frequency output wiring
Discrete output wiring
Discrete input wiring
9.1 Channel configuration
The six wiring terminals are divided into three pairs, and called Channels A, B, and C.
Channel A is terminals 1 and 2; Channel B is terminals 3 and 4; Channel C is terminals 5 and
6. Variable assignments are governed by channel configuration.
Channel configurationTable 9-1:
Channel Terminals Configuration options Power
A 1, 2 mA output with HART/Bell202 Internal
B 3, 4 mA output (default) Internal
Frequency output Internal or external
Discrete output Internal or external
C 5, 6 Frequency output (default) Internal or external
Discrete output Internal or external
Discrete input Internal or external
Notes
For Channel A, the Bell 202 signal is superimposed on the mA output.
You must provide power to the outputs when a channel is set to external power.
When both Channel B and Channel C are configured for frequency output (dual pulse),
frequency output 2 is generated from the same signal that is sent to the first frequency
output. Frequency output 2 is electrically isolated but not independent.
I/O wiring for Model 2700 transmitters with configurable input/outputs
90 Micro Motion
®
Model 1700 and 2700