Process variable Label
Display ProLink III FC
Concentration measurement
Density at reference Referred Density Density at Reference
Temperature
Dens at Ref (CM)
Specific gravity Specific Gravity Density (Fixed SG Units) Spec Gravity (CM)
Standard volume flow rate Standard Vol Flow Volume Flow Rate at
Reference Temperature
Stnadard Volume Flow Rate
Net mass flow rate Net Mass Flow Net Mass Flow Rate Net Mass Flow (CM)
Net volume flow rate Net Volume Flow Rate Net Volume Flow Rate Net Volume Flow Rate (CM)
Concentration Concentration Concentration Concentration (CM)
Baume Baume Baume Baume (CM)
Batching
% of batch delivered % of Fill % of Fill Delivered % of Fill Delivered
Energy measurement
Energy flow Energy Flow Energy Flow
Calorific value Calorific Value Calorific Value
8.2.2 Configure Lower Range Value (LRV) and Upper Range Value
(URV) for the mA Output
Display
Menu > Configuration > Inputs/Outputs > Channel x > I/O Settings > Lower Range Value
Menu > Configuration > Inputs/Outputs > Channel x > I/O Settings > Upper Range Value
ProLink III Device Tools > Configuration > I/O > Outputs > mA Output > Lower Range Value
Device Tools > Configuration > I/O > Outputs > mA Output > Upper Range Value
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mA Output xSettings > Lower
Range Value
Configure > Manual Setup > Inputs/Outputs > Channel x > mA Output x > mA Output xSettings > Upper
Range Value
The Lower Range Value (LRV) and Upper Range Value (URV) are used to scale the mA Output, that is, to
define the relationship between mA Output Process Variable and the mA Output signal.
LRV is the value of mA Output Source represented by an output of 4 mA. URV is the value of mA Output
Source represented by an output of 20 mA. Between LRV and URV, the mA Output is linear with the process
variable. If the process variable drops below LRV or rises above URV, the transmitter posts an output
saturation alert.
Procedure
Set LRV and URV as desired.
Enter LRV and URV in the measurement units used for mA Output Source.
Defaults: Specific to each process variable
Configuration and Use Manual Integrate the meter with the control system
MMI-20025166 March 2019