Emerson Micro Motion 5700 - Consistently Incorrect FO Measurement

Emerson Micro Motion 5700
356 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault condition if Fault Action is set to Internal Zero or Downscale
Two-phase flow
Flow in reverse direction from configured flow direction parameter
Frequency Output Direction not set correctly
Bad frequency receiving device
Output level not compatible with receiving device
Bad output circuit
Incorrect internal/external power configuration
Output not powered
Wiring problem
Channel not configured for desired output
Channel not configured for desired input
Channel not licensed
Recommended actions
1. Verify that the process conditions are below the low-flow cutoff. Reconfigure the low-flow cutoff if
necessary.
2. Check the Fault Action settings.
3. Verify that the totalizers are not stopped. A stopped totalizer will cause the Frequency Output to be
locked.
4. Check for two-phase flow.
5. Check flow direction.
6. Check the direction parameters.
7. Verify the receiving device, and the wiring between the transmitter and the receiving device.
8. Verify that the channel is wired and configured as a Frequency Output.
9. Purchase a license for the channel and upgrade the transmitter firmware.
10. Verify the power configuration for the Frequency Output (internal vs. external).
11. Perform a loop test.
17.10.2 Consistently incorrect FO measurement
Cause
Output not scaled correctly
Incorrect measurement unit configured for process variable
Recommended actions
1. Check the scaling of the Frequency Output.
2. Verify that the measurement units are configured correctly for your application.
Troubleshooting Configuration and Use Manual
March 2019 MMI-20025166
256 Micro Motion Model 5700 Transmitters with Configurable Outputs