2. Check your process conditions against the values reported by the device.
3. Adjust the Frequency Input using a K factor.
4. Ensure that the external device is operating correctly.
5. Verify the wiring between the transmitter and the external device.
17.13.51 Frequency Output 2 Fixed
Alert
Output Fixed
Cause
The output is configured to send a constant value. A loop test may be in progress.
Recommended actions
Check to see if a loop test is in process (the output is fixed).
17.13.52 Frequency Output 2 Saturated
Alert
Output Saturated
Cause
The calculated output value is outside the range of the output.
Recommended actions
1. Check the scaling of the Frequency Output.
2. Check your process conditions against the values reported by the device.
3. Ensure that both devices are using the same measurement unit.
4. Purge the sensor tubes.
17.13.53 mA Input Failure or Outside Range
Alert
Process Aberration
Cause
The mA Input signal is below 3.8 mA or above 20.5 mA.
Recommended actions
1. Verify the mA Input configuraion, especially Lower Range Value and Upper Range Value.
2. Verify that the external input device is operating correctly.
3. Verify the wiring between the transmitter and the external device.
4. Check your process conditions against the values reported by the device.
Configuration and Use Manual Troubleshooting
MMI-20025166 March 2019