52 PACMotion VFD AC Variable Speed Drive User Guide GFK-3111A
Example Connection Schematics
Table 29: Example Connection Schematics
P1-13 Setting: 1 4 11 14
+
_
+24 V DC*
1
+24 V DC +24 V DC +24 V DC +24 V DC +24 V DC
2
DI 1 Disable / Enable Disable / Enable Run Forward Run Forward
3
DI 2
Forward /
Reverse
Forward /
Reverse
Run Reverse Run Reverse
4
DI 3
P1-12 Reference /
PR Reference
P1-12 Reference /
PR Reference
P1-12 Reference /
PR Reference
P1-12 Reference /
PR Reference
5
+10 V DC +10 V DC +10 V DC +10 V DC +10 V DC
6
AI 1 Analog Input 1 Analog Input 1 Analog Input 1 Analog Input 1
7
0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM
8
AO 1
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
9
0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM
10
DI 5
Preset Speed Select
(P2-01 / P2-02)
Dec. Ramp Select
(P1-04 / P8-11)
Preset Speed Select
(P2-01 / P2-02)
Dec. Ramp Select
(P1-04 / P8-11)
11
AO 2
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
12
STO+ STO+ STO+ STO+ STO+
13
STO- STO- STO- STO- STO-
Table 30: Example Connection Schematics
P1-13 Setting: 2 8 9 12 18 19
+
_
+24 V DC*
1
+24 V
DC
+24 V DC +24 V DC +24 V DC +24 V DC +24 V DC +24 V DC
2
DI 1
Disable /
Enable
Disable /
Enable
Disable /
Enable
Run Forward Run Forward Run Forward
3
DI 2
Forward /
Reverse
Forward /
Reverse
Forward /
Reverse
Run Reverse Run Reverse Run Reverse
4
DI 3
Preset Speed
Select BIT 0
Preset Speed
Select BIT 0
Preset Speed
Select BIT 0
Preset Speed
Select BIT 0
Preset Speed
Select BIT 0
Preset Speed
Select BIT 0
5
+10 V
DC
+10 V DC +10 V DC +10 V DC +10 V DC +10 V DC +10 V DC
6
DI 4
Preset Speed
Select BIT 1
Preset Speed
Select BIT 1
Preset Speed
Select BIT 1
Preset Speed
Select BIT 1
Preset Speed
Select BIT 1
Preset Speed
Select BIT 1
7
0 V /
COM
0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM
8
AO 1
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
Analog Output 1
(Motor Speed)
9
0 V /
COM
0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM 0 V / COM
10
DI 5
Preset Speed
Select BIT 2
Dec. Ramp Select
(P1-04 / P8-11)
P1-12 Reference
/ Preset Ref
Dec. Ramp Select
(P1-04 / P8-11)
Dec. Ramp Select
(P1-04 / P8-11)
P1-12 Reference
/ Preset Ref
11
AO 2
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
Analog Output 2
(Motor Current)
12
STO+ STO+ STO+ STO+ STO+ STO+ STO+
13
STO- STO- STO- STO- STO- STO- STO-
NOTE * Optional external 24 V DC power supply