84 PACMotion VFD AC Variable Speed Drive User Guide GFK-3111A
Technical Data
Environmental
Table 54: Environmental Data
Ambient
Temperature
Storage and
Transportation
All Units -40 … 60°C / -40 … 140°F
Operating
IP20 Units
-10 … 50°C / 14 … 122°F
IP55 Units
- 10 … 40°C / 14 … 104°F UL Approved
40 … 50°C / 104 … 122°F
With derating (refer to section Table 62: Derating
for Ambient Temperature on page 88)
IP66 Units
- 10 … 40°C / 14 … 104°F UL Approved
40 … 50°C / 104 … 122°F
With derating (refer to section Table 62: Derating
for Ambient Temperature on page 88)
Altitude Operating All Units =<1000 m With UL approval
=<4000 m With derating (refer to section Table 63:
Derating for Altitude on page 88)
Relative Humidity
Operating All Units < 95% Non-condensing, frost and moisture free
Input/Output Power and Current Ratings
The following tables provide the output current rating information for the various PACMotion VFD models.
Emerson always recommend that selection of the correct PACMotion VFD is based upon the motor full load
current at the incoming supply voltage.
Please note that the maximum cable length stated in the following tables indicate the maximum permissible
cable length for the drive hardware and does not take into consideration EMC compliance.
Table 55: 200 – 240 Volt (+/- 10%),1 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW HP A
Non UL
UL mm AWG/kcmil A m ft Ω
2 0.75 1 8.6 16 15 8 8 4.3 100 330 100
2 1.5 1.5 12.9 16 17.5 8 8 7 100 330 50
2 2.2 3 19.2 25 25 8 8 10.5 100 330 35
Table 56: 200 – 240 Volt (+/- 10%), 3 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated Output
Current
Maximum Motor
Cable Length
Recommended
Brake Resistance
kW HP A
Non UL
UL mm AWG/kcmil A m ft Ω
2 0.75 1 5.7 10 10 8 8 4.3 100 330 100
2 1.5 2 10.5 16 15 8 8 7 100 330 50
2 2.2 3 13.2 16 17.5 8 8 10.5 100 330 35
3 4 5 20.9 32 30 8 8 18 100 330 20
3 5.5 7.5 26.4 32 35 8 8 24 100 330 20
4 7.5 10 33.3 40 40 16 5 30 100 330 22
4 11 15 50.1 63 70 16 5 46 100 330 22
5 15 20 63.9 80 80 35 2 61 100 330 12
5 18.5 25 74.0 100 90 35 2 72 100 330 12
6 22 30 99.1 125 125 150 300MCM 90 100 330 6
6A 22 30 80.6 100 100 150 300MCM 90 100 330 6
6 30 40 121.0 160 150 150 300MCM 110 100 330 6
6B 30 40 97.8 125 125 150 300MCM 110 100 330 6
6 37 50 159.7 200 200 150 300MCM 150 100 330 6
6B 37 50 139.7 200 175 150 300MCM 150 100 330 6
6 45 50 187.5 250 225 150 300MCM 180 100 330 6
6B 45 60 163.4 200 200 150 300MCM 180 100 330 6
6B 55 75 185.9 250 225 150 300MCM 202 100 330 6
7 55 50 206.5 250 250 150 300MCM 202 100 330 6
7 75 50 246.3 315 300 150 300MCM 248 100 330 6