▪ Supports the Remote Get HART
®
Device Information COMMREQ, which
allows the user application to read information from a HART device
connected to an RX3i Analog module in an IC695PNS001 RX3i PROFINET
Scanner. A UDFB that automates the COMMREQ control logic is available for
download. (Refer to New Features and Enhancements for additional
information.)
▪ Configured with Sequence of Events recording through the Embedded
PROFINET Controller when used with up to four IC695PNS101 Advanced
PROFINET Scanner modules. A RX3i SoE system supports events from up to
512 SoE input points with a system storage buffer for up to 128,000 events at
a maximum rate of 400 events per second per PNS101. Each PNS101
supports SoE recording with IRIG B time synchronization of events accurate
to 1ms and buffers up to 4000 events from up to four IC694MDL660
32 Circuit Discrete Input modules. Unmodulated IRIG B time signals are
decoded by the PNS101 using either an IC695HSC304 or IC695HSC308 High
Speed Counter Module. SoE recording is available in both simplex and
redundant PROFINET systems.
▪ Supports programming in Ladder Diagram, Structured Text, Function Block
Diagram, or C.
▪ Contains 64 Mbytes of configurable data and program memory.
▪ Supports auto-located Symbolic Variables that can use any amount of user
memory.