5 PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide GFK-2941K
Contains reference tables include 32k bits for discrete %I and %Q and up to
32k words each for analog %AI and %AQ. Bulk memory (%W) also supported
for data exchanges.
Supports up to 768 program blocks. Maximum size for a block is 128KB.
Configured to display serial number and date code in PME Device Information
Details.
Configured for Coordinated Universal Time (UTC) and Day Light Savings Time
(DST) support.
Operating temperature range 0 C to 60 C (32 F to 140 F).
Compliant with EU RoHS Directive 2002/95/EC using the following
exemptions identified in the Annex: 7(a), 7(c)-I and III, and 15.
Switches
The Run/Stop switch and RDSD UPLD and RDSD DNLD pushbuttons are
located behind the protective front door. Switch operation is given in the
following table.
The Run/Stop switch is enabled by default; it can be disabled in the PME
Hardware Configuration (HWC) settings. The memory protection function
of this switch can be disabled separately in HWC. The memory protection
functionality is disabled by default.