If Reference Selected Indicator (01.049) = 6 the Keypad Control Mode Reference (01.017) is used, but keypad control mode is not active.
Parameter 01.015 Preset Selector
Short description Defines which preset is used for the reference
Mode OpenLoop
Minimum 0 Maximum 9
Default 0 Units
Type 8 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
See Reference Selector (01.014).
Parameter 01.016 Preset Selector Timer
Short description Defines the time between changes of preset selector
Mode OpenLoop
Minimum 0.0 Maximum 400.0
Default 10.0 Units s
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
If Preset Selector (01.015) = 9 then Preset Selected Indicator (01.050) is incremented by one at intervals defined by Preset Selector Timer (01.016). When
Preset Selected Indicator (01.050) has a value of 8 and is incremented it rolls over to 1. If Preset Selector Timer Reset (01.048) = 1 and Preset Selector
(01.015) = 9, then Preset Selected Indicator (01.050) is held at 1.
Parameter 01.017 Keypad Control Mode Reference
Short description Defines the value of the keypad reference
Mode OpenLoop
Minimum −VM_SPEED_FREQ_KEYPAD_REF Maximum VM_SPEED_FREQ_KEYPAD_REF
Default 0.0 Units
Type 32 Bit Power Down Save Update Rate 4ms read
Display Format Standard Decimal Places 1
Coding RO, VM, NC, PT
Keypad control mode is active if the Reference Selected Indicator (01.049) is 4 or 6. The value of this parameter is controlled by the reference selector
system and whether Hand/Off/Auto mode is selected (see Hand/Off/Auto Operating Mode (01.052)). If keypad control is selected the frequency/speed
reference is defined by Keypad Control Mode Reference (01.017) which is a read-only parameter. The parameter can only be adjusted by pressing the Up
or Down keys when the keypad is in Status Mode and only when keypad control mode is active. Holding the Up or down keys auto-increments or
decrements Keypad Control Mode Reference (01.017), and the rate of adjustment increases the longer the key is held. Keypad Control Mode Reference
(01.017) can be adjusted whether the drive is enabled or not, and can be retained at power-down if required (see Power-
up Keypad Control Mode Reference (01.051)).
If the Reference Selected Indicator (01.049) is 6 then the normal drive sequencer is used and the run commands are derived from the sequencer control bit
parameters. If Reference Selected Indicator (01.049) is 4 then the keypad control sequencer is used and the drive run commands are derived using keys
on the keypad. If the keypad control sequencer is active the Stop and Run keys automatically become active and the Auxilliary key may be optionally
enabled as the reverse key with Enable Auxiliary Key (06.013).
Parameter 01.021 Preset Reference 1
Short description Defines the value for preset reference 1
Mode OpenLoop
Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF
Default 0.0 Units
Type 32 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 1
Coding RW, VM
See Reference Selector (01.014).
Parameter 01.022 Preset Reference 2
Short description Defines the value for preset reference 2
Mode OpenLoop
Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF
Default 0.0 Units
Type 32 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 1
Coding RW, VM
See Reference Selector (01.014).
26
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00