Range Limits Note
This screen verifies your 4–20 mA range values when you send a new
flow configuration to a transmitter. It shows the current values and
allows you to either confirm or change them. If you select Change, the
Range Values screen appears (see page 6-45).
Maintenance Screens Maintenance Privileges
This screen allows changing password security levels. For information
concerning passwords, see page 6-47.
Maintenance Sensor Trim
The sensor trim screens are used during bench and field calibration of
the Mass ProPlate.
In addition to the EA Software, the following equipment is required for
a sensor trim procedure:
• Mass ProPlate
• Dead-weight tester
• Power supply and load resistor
• Vacuum pump or a barometer that is at least 3 times as accurate
as the Mass ProPlate AP sensor. A barometer is preferred.
Table 6-2 identifies the LRL and URL for the Mass ProPlate.
Figure 6-38.
Range Limits Note.
Figure 6-39.
Privileges Screen.