2-17
Figure 2-19.
Steam Service in a Horizontal Pipe.
Liquid Service in a Vertical Pipe
The Mass ProPlate can be installed anywhere around the
circumference of the pipe, as shown in Figure 2-20. The transmitter
should always be remote mounted below the meter assembly.
Figure 2-20.
Liquid Service in a Vertical Pipe.
Gas Service in a Vertical Pipe
The Mass ProPlate can be installed anywhere around the
circumference of the pipe, as shown in Figure 2-21. The transmitter
should always be remote mounted above the meter assembly.