Figure 5-2: Grounding
DP
A
B
C
D
E
A. Trim shield and insulate
B. Insulate shield
C. Terminate cable shield drain wire to earth ground
D. Internal ground location
E. External ground location
5.1 Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing
and inside the terminal compartment. These grounds are used when the
transient protection terminal blocks are installed. It is recommended that 18
AWG or larger wire is used to connect housing ground to earth ground
(internal or external).
If the transmitter is currently not wired for power up and communication,
follow Connect the wiring and power up. When the transmitter is properly
wired, refer to Figure 5-2 for internal and external transient grounding
locations.
Quick Start Guide May 2019
12 Emerson.com/Rosemount