cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Appropriate cable, glands and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature
for location where installed.
I1 ATEX Intrinsic Safety
Certificate
BAS00ATEX1166X
Standards
EN60079-0:2012 + A11:2013, EN60079-11:2012
Markings
Ex II 1 G Ex ia IIC T4 Ga (–55 °C ≤ T
a
≤ +70 °C)
Table 9-2: Input Parameters
HART
Voltage U
i
30 V
Current I
i
200 mA
Power P
i
0.9 W
Capacitance C
i
0.012 μF
Special Conditions for Safe Use(X)
1. The apparatus is not capable of withstanding the 500 V insulation
test required by EN60079-11. This must be taken into account when
installing the apparatus.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in a Zone 0 environment.
N1 ATEX Type n
Certificate
BAS00ATEX3167X
Standards
EN60079-0:2012 + A11:2013, EN60079-15:2010
Markings
Ex II 3 G Ex nA IIC T5 Gc (–55 °C ≤ T
a
≤ +70 °C)
Special Conditions for Safe Use(X)
1. This apparatus is not capable of withstanding the 500V insulation
test required by EN60079-15. This must be taken into account when
installing the apparatus.
ND ATEX Dust
Certificate
BAS01ATEX1427X
May 2019 Quick Start Guide
Quick Start Guide 25