Standards
EN60079-0:2012 + A11:2013, EN60079-31:2009
Markings
Ex II 1 D Ex t IIIC T50 °C T
500
60 °C Da
Special Conditions for Safe Use(X)
1. Cable entries must be used which maintain the ingress protection of
the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable blanking plugs
which maintain the ingress protection of the enclosure to at least
IP66.
3. Cable entries and blanking plugs must be suitable for the ambient
range of the apparatus and capable of withstanding a 7J impact test.
9.4 International
E7 IECEx Flameproof
Certificate
IECEx KEM 06.0021X
Standards
IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-26:2014
Markings
Ex db IIC T6…T4 Ga/Gb T6(–60 °C ≤ T
a
≤ +70 °C), T5/T4(–60 °C
≤ T
a
≤ +80 °C)
Table 9-3: Process Connection Temperature
Temperature class Process connection
temperature
Ambient temperature
T6 –60 to +70 °C –60 to +70 °C
T5 –60 to +80 °C –60 to +80 °C
T4 –60 to +120 °C –60 to +80 °C
Special Conditions for Safe Use(X)
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between zone 0 (process connection) and
zone 1 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer’s instructions for installation and maintenance
shall be followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.