WRITE PROTECT
The write protect (SECURITY) jumper is set to disable changes to the
transmitter configuration data. Refer to “Transient Protection Terminal Block”
on page 2-21 for more information on the security jumper.
Field Communicator Diagnostics
Table 5-2 is a list of messages used by the Field Communicator (HC) and
their corresponding descriptions.
Variable parameters within the text of a message are indicated with
<variable parameter>.
Reference to the name of another message is identified by
[another message].
Table 5-2. Field Communicator
Messages
Message Description
1k snsr EEPROM
error-factory ON
Replace the transmitter
1k snsr EEPROM
error-user-no out ON
Use the Field Communicator to reset the following
parameters: remote seal isolator, remote seal fill fluid,
flange material, o-ring material, transmitter type, remote
seal type, flange type, meter type, number of remote
seals.
1k snsr EEPROM
error-user ON
Perform a full trim to recalibrate the transmitter.
4k micro EEPROM
error-factory ON
Replace the electronics board.
4k micro EEPROM
error-user-no out ON
Use the Field Communicator to reset the message field.
4k micro EEPROM
error-user ON
Use the Field Communicator to reset the following
parameters: units, range values, damping, analog output,
transfer function, tag, scaled meter values. Perform a D/A
trim to ensure that the error is corrected.
4k snsr EEPROM
error-factory ON
Replace the transmitter.
4k snsr EEPROM
error-user ON
Use the Field Communicator to reset the temperature
units and the calibration type.
Add item for ALL device types
or only for this ONE device type.
Asks the user whether the hot key item being added
should be added for all device types or only for the type of
device that is connected.
Command Not Implemented The connected device does not support this function.
Communication Error The communicator and the device are not communicating
correctly. Check all connections between the Field
Communicator and the device and resend the
information.
Configuration memory not
compatible with connected
device
The configuration stored in memory is incompatible with
the device to which a transfer has been requested.
CPU board not initialized ON The electronics board is not initialized.
Replace the electronics board.
CPU EEPROM write failure ON Message sent to electronics board from HART signal
failed. Replace the electronics board.
Device Busy The connected device is busy performing another task.
Device Disconnected The device failed to respond to a command. Check all
connections between the Field Communicator and the
device and resend the command.
Device write protected Device is in write-protect mode. Data can not be written.