Standards:
IEC60079-0:2011, IEC60079-11:2011
Markings:
Ex ia IIC T4 Ga (–55 °C ≤ T
a
≤ +70 °C)
Table 8-4: Input Parameters
Parameter HART
Voltage U
i
30 V
Current I
i
200 mA
Power P
i
0.9 W
Capacitance C
i
0.012 µF
Special Conditions for Safe Use (X):
1. When fitted with a transient suppression terminal block, the
Rosemount 2088 is incapable of passing the 500 V isolation test. This
must be taken into account during installation.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it
from impact or abrasion if located in a Zone 0 environment.
IECEx Type n
Certificate:
IECEx BAS 12.0072X
Standards:
IEC60079-0:2011, IEC60079-15:2010
Markings:
Ex nA IIC T5 Gc (–40 °C ≤ T
a
≤ +70 °C)
Special Condition for Safe Use (X):
1. When fitted with a transient suppression terminal block, the
Rosemount 2088 is incapable of passing the 500 V isolation test. This
must be taken into account during installation.
NK IECEx Dust
Certificate:
IECEx BAS12.0073X
Standards:
IEC60079-0:2011, IEC60079-31:2008
Markings:
Ex t IIIC T50 °C T
500
60 °C Da
Table 8-5: Input Parameters
Parameter HART
Voltage U
i
36 Vdc
Quick Start Guide March 2022