2 Overview
2.1 Introduction
The Rosemount
2410 Tank Hub collects measurement data and status information from
field devices designed for the Rosemount Tank Gauging system via the intrinsically safe 2-
wire Tankbus
(1)
. The Tankbus carries both data transmission and power supply (see also
Tankbus).
Figure 2-1: System Integration
%
,
&
$
(
)
01
*
+
-
/
'
.
2
3
A.
Rosemount TankMaster I. Rosemount 2410 Tank Hub
B. Rosemount 2460 System Hub J. Tankbus
C. Modem K. Secondary bus (IS)
D. Host L. Rosemount 2230 Field Display
E. Servo gauges M. Rosemount 5900S Radar Level Gauge
F. Secondary Bus (Non-IS) N. Rosemount 2240S Temperature Transmitter
G. Relay Outputs O. Zone 1
H. Primary Bus P. Zone 0
The Rosemount 2410 is designed for use in hazardous area Zone 1 (Class 1, Division 1) and
communicates with field devices in Zone 1 via the intrinsically safe Tankbus.
The Rosemount 2410 is available in two versions for single tanks or multiple tanks. The
multiple tanks version supports up to 10 tanks and 16 devices.
(1)
The intrinsically safe Tankbus complies with the FISCO FOUNDATION
Fieldbus standard.
Reference Manual Overview
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 11