5. Set the communication parameters:
Table 3-1: Communication Parameters
FBM RS485 converter
Port The COM port the FBM is
connected to
The COM port the converter is
connected to
Baud rate 4800 9600
Stop bits 1 1
Parity None None
Modem FBM 2180 RS-485
Handshaking None RTS/CTS
Reply timeout 1000 ms 1000 ms
Retries 3 3
Description Text describing the configured
channel
Text describing the configured
channel
6. Select the Enable Channel check box to activate the protocol channel.
7. Select OK to store the current configuration and close the configuration window.
3.2  Install Rosemount 2410 Tank Hub in WinSetup
The TankMaster WinSetup wizard is the recommended tool for installing the tank hub. The
installation wizard manages basic configuration of the tank hub.
Perform the following steps to start the installation wizard in TankMaster WinSetup:
Procedure
1. In the TankMaster WinSetup workspace window select the Devices folder.
2. Right click and select Install New or, from the Service menu, select the Devices/
Install New option. The Select Device window opens.
Configuration Manual Supplement
August2023 00809-0800-2410
14 Emerson.com/Rosemount