7. Default Modbus Address is 247 for the tank hub. It is recommended to change it to
an address between 101-199. To change the adress, do the following:
a) In the 2410 Tank Hub Communication window select Change Address on
Device... to open the Change Address window.
b) Enter the Unit ID and select the new Modbus Address. When changing the
device address, the Unit ID is used as a unique identifier of the device. The
Unit ID can be found on a label mounted on the device.
c) Select OK to confirm the address settings and close the Change Address
window.
d) In the 2410 Tank Hub Communication window select Verify Communication
to check that communication is established between the TankMaster work
station and the tank hub. The Unit ID will appear when TankMaster detects
the tank hub.
8. In the 2410 Tank Hub Communication window select Next to continue the
installation procedure of the tank hub.
9. Continue configuration of the tank hub following the standard installation
procedure.
3.3 
Configure specific variables for emulation
The tank hub holding registers are used to configure the Sakura emulation variables.
Procedure
1. In the TankMaster WinSetup workspace window, right click the tank hub device icon.
2. To view the holding registers, select the View Holding Registers option.
Note
When replacing a Sakura gauge with a Rosemount device, the Rosemount device
must have the same Sakura address as the gauge being replaced.
Configuration Manual Supplement
August2023 00809-0800-2410
16 Emerson.com/Rosemount