5.11 Digital input
The K1 and K2 relay input status can be included in the Sakura V1 protocol response. The
digital input value is customized as shown in Table 5-9.
Table 5-9: Digital Input Values
Value Decoded
ASCII char
Description
30h 0 K1 and K2 energized (or function disabled by holding register
MiscCtrl bit 6, see Table 5-6)
31h 1 K1 de-energized and K2 energized
32h 2 K1 energized and K2 de-energized
33h 3 K1 and K2 de-energized
Note
This function must be enabled by the MiscCtrl register status bit 6. See Table 5-6.
5.12 Pressure value
There are three pressure values in the Sakura V1 protocol: P1, P2, and P3. They are by
default configured as:
• P1: Liquid pressure
• P2: Middle pressure
• P3: Vapor pressure
For backward compatibility with Rosemount Rex, the Liquid pressure value can be
remapped to P2 and/or P3. This is done in holding register Sakura_PressConf (1214). If
Liquid pressure is remapped, Vapor pressure will be used for the other pressure requests
that are not remapped.
Table 5-10: Holding Register 1214, Bit Configuration
Bit 2,
P3_Liquid
Bit 1,
P2_Liquid
Bit 0,
P1_Liquid
Pressure values
0 0 0 Default: P1 = Liquid pressure, P2 = Middle pressure and P3 =
Vapor pressure
0 0 1 P1 = Liquid pressure, P2 = Middle pressure and P3 = Vapor
pressure
0 1 0 P2 = Liquid pressure, P1 = P3 = Vapor pressure
0 1 1 P1 = P2 = Liquid pressure, P3 = Vapor pressure
1 0 0 P3 = Liquid pressure, P1 = P2 = Vapor pressure
1 0 1 P1 = P3 = Liquid pressure, P2 = Vapor pressure
1 1 0 P2 = P3 = Liquid pressure, P1 = Vapor pressure
1 1 1 P1 = P2 = P3 = Liquid pressure.
Optional configuration and settings Manual Supplement
August2023 00809-0800-2410
30 Emerson.com/Rosemount