105
Reference Manual
00809-0100-2460, Rev DE
Service and Troubleshooting
October 2018
Service and Troubleshooting
6.2 Tools
The following standard tools are needed for service and maintenance of the Rosemount
2460:
Screwdriver (Flat or Phillips)
Wrench (Metric fixed or adjustable)
Torx size 20 and 30 (for opening the lid and exchanging spare parts)
6.3 Troubleshooting
Table 6-1 on page 105 provides summarized maintenance and troubleshooting suggestions for the most
common operating problems.
Table 6-1. Troubleshooting chart
Symptom Possible cause Action
No contact with the
Rosemount 2460 System
Hub
Wiring
Check that wires are properly connected to the
terminals.
Check for dirty or defective terminals.
Check wire insulation for possible short circuits to
ground.
Check that the Rosemount 2460 System Hub is
connected to the right communication port on the
control room PC.
RS485 wiring
Check for proper polarity at the terminals.
Field Bus Modem (FBM 2180)
Check that the Tx and Rx LEDs on the FBM are
blinking to verify proper communication with the
FBM.
Check that the FBM is connected to the right port
on the control room PC.
Check that the FBM is connected to the right port
on the Rosemount 2460 System Hub.
Connection to Rosemount
2460 System Hub
Check communication port LED:s inside the
Rosemount 2460. Next to each modem card is a
green and a yellow LED for Tx and Rx signals. The
LEDs will blink if communication is working
properly.
Configuration of Rosemount
2460 System Hub
Check the communication address for the
Rosemount 2460. Connect a service PC to the
Ethernet 3 port and open the Web
Interface>Communication tab.
Check configuration of communication parameters
for the Rosemount 2460 host ports. Connect a
service PC to the Ethernet 3 port and open the Web
Interface>Communication tab.
Check that the correct communication channel is
selected.