208
Fast Polling
Fast Polling
October 2018
Reference Manual
00809-0100-2460, Rev DE
Configure fast polling with individual settings
1. Open TankMaster WinSetup. Ensure that Individual Settings is enabled. See “Enable individual
settings” on page 206.
2. In the WinSetup workspace, click the right mouse button on the Rosemount 2460 icon and choose
Properties.
3. Select the Tank Database tab.
4. Click the Advanced button for the desired tank to open a configuration window. It may differ for
various devices as shown below.
5. The configuration window lets you specify Fast Polling parameters for the selected tank.
6. Set the desired Hysteresis and Threshold values. These values will apply to the tank that was
selected in the Rosemount 2460’s tank database. Individual threshold settings can be configured for
other tanks as well by using the Advanced button for those tanks.
7. Press OK to save the current configuration and close the window.
Advanced button