210
L&J Device Configuration
L&J Device Configuration
October 2018
Reference Manual
00809-0100-2460, Rev DE
3. Find a free tank position (2460 Tank 1, 2, 3...) for the device to be configured.
4. In the Source field, choose the appropriate L&J device type.
5. Select the Field Port that the device is connected to. Ensure that the port is equipped with the
appropriate modem. In the standard configuration there are six field bus ports available for the
Rosemount 2460 System Hub. See “Connecting to a Rosemount 2460 System Hub” on page 30 for
more information.
6. Enter the address of the gauge into the Level Device Address field. Each field device has its own
unique address in the range 0-127.
7. The Temp Device Address field can not be edited. The address is automatically set to the address of
the level device.
8. Select the Auxiliary Inputs that are used for the device. Vapor Pressure (VP), Liquid Pressure (LP), Free
Water Level (FWL), and User Input 1 (UIn1) can be configured for L&J devices.
See Table H-1 on page 211 for a list of available Auxiliary Inputs.
Note that only one pressure parameter at a time may be chosen, i.e. either the VP or the LP
parameter.
9. See “Advanced L&J configuration” on page 212 for advanced options.