J.3 Host port configuration
The Configuration window lets you setup communication ports for Enraf 858 CIU emulation.
1. In the TankMaster Winsetup workspace, click the right mouse button on the Rosemount 2460 icon.
2. Select Properties to open the system hub’s configuration window.
3. Identify the port that is used for the Enraf CIU 858 emulation.
4. In case port 5 or 6 is used for Enraf CIU 858 communication, verify that protocol type is HostPort. If
not, select Host Port from the drop-down list.
5. Verify correct Protocol and communication settings. Click the Advanced button if you need to
change any communication settings. Note that Ports 5 and 6 can be used as either field or host ports.
Ports 7 and 8 can be used as Host Ports only.
In the default setup, ports 1 - 6 are are configured as field ports. Note that only port 7 can be used for
RS232 communication with the Enraf host.