6 Verify configuration parameters
Emerson recommends that you verify various configuration
parameters prior to installing the transmitter into the process:
• Alarm and saturation levels
• Damping
• Process variables
• Range values
• Tag
• Transfer function
• Units
See Figure 6-1 for a full menu tree.
NOTICE
Emerson recommends installing the latest device descriptor (DD) to
ensure full functionality. Download the latest DD at Software &
Drivers.
Procedure
1. Set alarm and saturation values: Device Settings → Setup
Overview → Alarm and Saturation Values.
2. Set damping: Device Settings → Setup Overview → Output.
3. Set process variables:
• Primary variable: Device Settings → Setup Overview →
Output
• Secondary/tertiary/quaternary variables: Device Settings →
Communication → HART → Variable Mapping
4. Set range values: Device Settings → Setup Overview → Output.
5. Set tag: Device Settings → Setup Overview → Device.
6. Set transfer function: Device Settings → Setup Overview →
Output.
7. Set units:
• Pressure units: Device Settings → Setup Overview →
Output
February2024 Quick Start Guide