7.0 Product Certifications
Rev 1.15
7.1 European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EU Declaration of Conformity can
be found at Emerson.com/Rosemount
.
7.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited by
the Federal Occupational Safety and Health Administration (OSHA).
7.3 Installing Equipment in North America
The US National Electrical Code
®
(NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined in
the respective codes.
7.4 USA
E5 FM Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: FM16US0090
Standards: FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 – 2011,
FM Class 3810 – 2005, ANSI/NEMA
®
250 – 2003
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP E, F, G; CL III;
T5(–50 °C T
a
+85 °C); Factory Sealed; Type 4X
I5 FM Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: FM16US0089X
Standards: FM Class 3600 – 2011, FM Class 3610 – 2010, FM Class 3611 – 2004,
FM Class 3810 – 2005, NEMA 250 – 2003
Markings: IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1,
Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D;
T4(–50 °C T
a
+70 °C) [HART]; T4(–50 °C T
a
+60 °C) [Fieldbus];
when connected per Rosemount drawing 03151-1006; Type 4X
Special Condition for Safe Use:
1. The Rosemount 3051S/3051S-ERS Pressure Transmitter contains aluminum and is
considered to constitute a potential risk of ignition by impact or friction. Care must be
taken into account during installation and use to prevent impact and friction.
Note
Transmitters marked with NI CL 1, DIV 2 can be installed in Division 2 locations using
general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing
03151-1006.