Quick Start Guide
19
March 2018
Special Conditions for Safe Use (X):
1. The Model 3051S Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.3.13 of EN 60079-11:2012. This
must be taken into account during installation.
2. The terminal pins of the Model 3051S SuperModule must be provided with a degree of
protection of at least IP20 in accordance with IEC/EN 60529.
3. The Model 3051S enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; however, care should be taken to protect it from impact or
abrasion if located in a zone 0 area.
IG IECEx Intrinsic Safety – Group I - Mining (IG with Special A0259)
Certificate: IECEx TSA 14.0019X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings: FISCO FIELD DEVICE Ex ia I Ma (–60 °C ≤ T
a
≤ +70 °C)
Special Conditions for Safe Use (X):
1. If the apparatus is fitted with optional 90 V transient suppressor, it is not capable of
withstanding the 500 V insulation test required by Clause 6.3.13 of
IEC60079-11:2011. This must be taken into account when installing the apparatus.
2. It is a condition of safe use that the above input parameters shall be taken into account
during installation.
3. It is a condition of manufacture that only the apparatus fitted with housing, covers and
sensor module housing made out of stainless steel are used in Group I applications.
N7 IECEx Type n
Certificate: IECEx BAS 04.0018X
Standards: IEC 60079-0:2011, IEC 60079-15:2010
Markings: Ex nA IIC T5 Gc, (–40 °C ≤ T
a
≤ +85 °C)
Special Condition for Safe Use (X):
1. The equipment is not capable of withstanding the 500 V insulation test required by
clause 6.5 of EN 60079-15:2010. This must be taken into account when installing the
equipment.
Parameter
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
Parameter
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0