Table 5-1: Diagnostic Message Troubleshooting (continued)
LCD display messages Host diagnostic
message
Possible problems Recommended
actions
SNSR INCOMP ERROR Sensor Module
Incompatibility
The SuperModule
assembly is not
compatible with the
feature board
electronics. The
SuperModule assembly
is not equipped with a
differential pressure
sensor or it is an older
revision of the sensor
module.
Replace the
SuperModule assembly
with one that is
compatible with the
Rosemount 3051SMV
Plantweb
™
Housing.
SNSR MISSING ERROR Sensor Missing The sensor mapped to
the primary variable is
not present.
Remap the primary
variable to a sensor
that is present.
SNSRT LIMIT Sensor Temperature
Out of Limits
The Sensor Module
Temperature is
exceeding the sensor
limits.
Verify ambient
conditions are within
the sensor limits.
XMTR Info Non-Volatile Memory
Warning
Transmitter
information data is
incomplete.
Transmitter operation
will not be affected.
Replace the feature
board electronics at
next maintenance
shutdown.
XMTR Info Error Non-Volatile Memory
Error
Non-volatile data of
the device is
corrupted.
Replace the feature
board electronics.
(Other message)
(1)
Maintenance Required The transmitter may
not be operating
properly and requires
attention.
Check other warning
messages.
(Other message)
(1)
mA Output Fixed The 4–20 mA analog
output signal is fixed at
a constant value and is
not representative of
the HART primary
variable.
Disable loop current
mode.
(Other message)
(1)
Primary variable out of
limits
The primary variable is
outside the range of
the transmitter.
View other diagnostic
messages to
determine which
variable is out of limits.
(Other message)
(1)
Non-primary variable
out of limits
A variable other than
the primary variable is
outside the range of
the transmitter.
View other diagnostic
messages to
determine which
variable is out of limits.